STUDI TENTANG DAYA REAKTIF SISTEM DISTRIBUSI JALUR B RSG-GAS

Yan Bony Marsahala

Sari


STUDY FOR REACTIVE POWER ON DISTRIBUTION SYSTEM LINE B RSG-GAS. Study for reactive power on distribution system line B RSG-GA is already done. The study intended to evaluate how much inductive load need the reactive power (positive), how much power factor, and what will be done to increase the power factor. The reactive power is the losses power, can't be changed into energy, but it is need for transmission process and it is cause the energy losses. The loads on distribution system line B consist of induction motors which are used for primary cooling system and secondary cooling system, lift, blower on cooling tower, and air condition system. Due to the motors using, the power factor are falling down to low. By the calculation results give that the inductive loads on distribution line Bare 850 KVA and these loads caused the low power factor 0.80. If we want to increase the power factor up to 0, 95, it is need to install the reactive loads likes capacitor bank 250 KVAR.