FAULT TREE ANALYSIS (FTA) POTENSI LEDAKAN GAS HIDROGEN PADA SISTEM TUNGKU REDUKSI ME-11 PROSES PEMBUATAN BAHAN BAKAR NUKLIR PLTN

Achmad Suntoro

DOI: http://dx.doi.org/10.17146/urania.2012.18.2.641

Sari


ABSTRAK

FAULT TREE ANALYSIS (FTA) POTENSI LEDAKAN GAS HIDROGEN PADA SISTEM TUNGKU REDUKSI ME-11 PROSES PEMBUATAN BAHAN BAKAR NUKLIR PLTN. Telah dibuat diagram Fault Tree Analysis (FTA)  untuk potensi ledakan gas hidrogen pada tungku reduksi ME-11 setelah kendali logik-nya ditambah (modifikasi). Diagram FTA ini dapat digunakan sebagai informasi tambahan dalam pembuatan program perawatan berkala dan langkah operasi dari tungku tersebut. Bertemunya dua kondisi yaitu pemicu ledakan dan komposisi gas hidrogen yang berpotensi meledak adalah fokus pencarian dalam FTA ini, dan dilakukan dengan cara mengurai dan merunut sistem tungku hingga ke penyebab awal dari dua kondisi tersebut bisa terjadi dalam waktu yang bersamaan. Dua lokasi berpotensi meledak teridentifikasi yaitu di ruang tungku dan di ruang pembakaran gas buang. Kemungkinan pemicu ledakan hanya berasal dari letikan api, api, dan benda panas, karena ME-11 tidak menggunakan gas hidrogen bertekanan tinggi. Namun demikian pemicu ledakan tersebut menjadi bagian dari proses reduksi yang berjalan, sehingga komposisi volume gas hidrogen selama proses berlangsung harus selalu diwaspadai.

Kata kunci: fault tree analysis, tungku reduksi, potensi ledakan hydrogen, pemicu ledakan hydrogen.

 

ABSTRACT

A FAULT TREE ANALYSIS (FTA) OF HYDROGEN EXPLOSION POTENTIALITY ON REDUCTION FURNACE ME-11 IN NUCLEAR POWER FUEL ELEMENT FABRICATION PROCESS. Fault Tree Analysis (FTA) diagrams for the potentiality of hydrogen gas explosion in reduction furnace of ME-11 has been created after modification of its logic control​​. These FTA diagrams can be used as additional information in designing preventive maintenance program and operational steps of the furnace. The encountering of two conditions, i.e. explosion ignition and the potentially explosive of hydrogen gas, is the search focus of the FTA, and it may be done by breaking and tracing down to any possibility of initial causes for these two conditions to occur coincidently. Two locations of the potentially explosive area were identified: furnace chamber and combustion chamber of the exhaust gas. The possible explosion ignitions for the furnace are only from spark, fire and hot material because the operation of the furnace does not use high-pressure hydrogen. However, these explosion ignitions are part of the on going reduction process, therefore it is important that the hydrogen gas volume composition during the process always be supervised.

Keywords: Fault Tree Analysis, reduction furnace, hydrogen explosion potentiality, hydrogen explotion ignition.


Teks Lengkap:

PDF

Refbacks

  • Saat ini tidak ada refbacks.


Penerbit: Pusat Riset Teknologi Bahan Nuklir dan Limbah Radioaktif 

Diindeks oleh:

   
     
      

p-ISSN 0852-4777 | e-ISSN 2528-0473

 

slot gacor slot