EVALUASI PENYEBAB SCRAM PADA KANAL UBL SISTEM PROTEKSI REAKTOR DALAM PENGOPERASIAN REAKTOR RSG-GAS

Jaja Sukmana, Rachmat Triharto, Irwan Irwan

DOI: http://dx.doi.org/10.17146/bprn.2017.14.1.3887

Sari


EVALUASI PENYEBAB SCRAM PADA KANAL UBL - SISTEM PROTEKSI REAKTOR DALAM PENGOPERASIAN REAKTOR RSG-GAS. Keselamatan dalam pengoperasian reaktor diterapkan oleh Sistem Proteksi Reaktor dengan tindakan scram. Namun scram yang sering terjadi merupakan kegagalan operasi dan menimbulkan risiko lain. Tujuan dari penelitian ini untuk mengetahui pemicu dan penyebab dasar terjadinya scram dengan metode deskriptif analitik melalui wawancara, observasi, dan telaah dokumen yang dipadukan dengan penyusunan fault tree analysis. Hasil deskriptif analitik menyatakan bahwa pemicu timbulnya scram, yaitu kerapatan fluks neutron terlalu tinggi, periode pengoperasian terlalu cepat, pembebanan atau daya di teras tidak merata, dan terjadinya transien reaktivitas positif. Sedangkan penyebab dasar kejadian scram pada kanal unbalanced load, terdiri dari kegagalan sistem instrumentasi, kondisi fluks neutron tidak merata, jatuhnya salah satu batang kendali, terjadinya pengosongan tabung berkas, gangguan handling dan loading sampel iradiasi, dan terjadi panas lokal pada elemen bakar. Karenanya fungsi scram sebagai antisipasi kecelakaan juga menjadi umpan balik pengalaman operasi untuk rekomendasi pemutakhiran penilaian keselamatan sehingga kegagalan operasi dapat diminimalisir.

 

Kata kunci: Keselamatan operasi reaktor nuklir; Penyebab kejadian; Scram reaktor; Sistem proteksi reaktor.

 

ABSTRACT

 

SCRAM CAUSE EVALUATION OF UNBALANCED LOAD CHANNEL - REACTOR PROTECTION SYSTEM AT OPERATION OF THE RSG-GAS REACTOR. Safety in the operation of the Reactor Protection System is implemented by the scram action. However scram which often happened is the failure of the operation and poses other risks. The purpose of this study is to determine the trigger and the reasons for scram with analytic descriptive method through interviews, observation and document review, combined with the preparation of fault tree analysis. The analytic descriptive results show that trigger of scram are, the neutron flux density is too high, too fast operation period, unbalanced load, and the occurrence of positive transient reactivity. While the basic causes of the scram incident on channel unbalanced load, consisting ofthe failure of instrumentation systems,neutron flux uneven conditions, the fall of one of control rods, the emptying of the beam tube, interference handling and loading of samples irradiated, and the local hot channel at the fuel elements. Therefore fungction of scram as anticipation of the accident is also the feedback of operating experience  for updating on safety assessment so that failure of the operation can be minimized.

 

Keywords:  Cause of the incident; Reactor protection system; Suddenly shutdown of reactor; The safe operation of nuclear reactor.


Teks Lengkap:

PDF

Refbacks

  • Saat ini tidak ada refbacks.


##submission.copyrightStatement##



Reaktor : Buletin Pengelolaan Reaktor Nuklir bekerjasama dengan:

     Creative Commons License 

slot gacor slot